TT-510 X
Heating and Cooling Unit
For temperatures from 80°C up to 300°C
Heating capacity 96 kW
Operational use:
rollers, plates, double walled vessels and other heavy duty use
TECHNICAL DATA: |
||
Temperature range | up to 300°C with heat transfer oil TOOL-THERM SH-3 | |
Temperature control | self-optimizing, electronic microprocessor controller MP-888 with digital display of the set and actual value. Automatic temperature monitoring. |
|
Flow control | electronically, with digital display and automatic control of the minimum flow. | |
Heating capacity | 96 kW | |
Switchable in stages | 16 / 16 / 16 / 16 / 16 / 16 | |
automatic shut down of the heating capacity which is not required. | ||
Cooling capacity | max. 480 kW – see diagram | |
Pump capacity | motor 4 kW | |
Pressure mode | max. 4 bar / max. 260 l/min | |
Cooling water consumption | 110 l/min (minimum 40 l/min, but leads to strong reduction of cooling capacity) | |
Expansion tank capacity | 130 litres | |
Filling Amount | 125 litres | |
Expansion volume | 100 litres | |
Connections | ||
Oil circuit | Flange connection DN 32 | |
flange-outside Ø 140 mm, with 4 holes Ø 18 mm on a screw hole circle of 100 mm recommended ceiling: 80 x 42 x 2 mm |
||
Cooling water | 1 1/2″ BSP female thread (required water pressure 1.5 – 4 bar) | |
Dimensions (L×W×H) | 2’150 × 1’300 × 1’950 mm | |
Weight | approx. 845 kg empty | |
Colour | silvergrey RAL 7001 |
Options:
MP-988 Microprocessor Controller for Digital Interfaces (RS-485 / RS-232 / Current Loop 20mA / CAN-bus / Profibus)
All possible voltages are available from 3 x 200 V to 3 x 600 V and 50/60 Hz.
The units are available conform to UL/CSA specifications. For the USA market the units are equipped with NPT-thread connections and the controller is adjusted to indicate °F.