TT-54’500 WK

TT-54’500 WK

Water Chiller
Water cooled water chiller with integrated heating capability for the water circuit
Mobile unit for individual machines or multi-machine applications

For water temperatures from +10°C up to +40°C,
at ambient temperatures up to +45°C

Suitable for high ambient air and tropical installations

TECHNICAL DATA:

Temperature control self-optimizing, electronic microprocessor controller MP-888 with digital display of the set and actual value.
Automatic temperature monitoring.
Flow control electronically, with digital display and automatic control of the minimum flow.
Cooling capacity
Nominal
54 kW – see diagram
Temperature range
Circulating water +10°C up to +40°C
Air temperature +10°C up to +40°C
Content water tank approx. 250 litres
Refrigerating agent R-134a
Pump capacity max. 6,2 bar / max. 250 l/min – see pump diagram
Compressor hermetically sealed
Condenser air cooled, air inlet located on the side, blow out located on the top
Air volume 8’000 m3/h (not relevant to WK)
Power consumption approx. 18 kW (heating mode approx. 18 kW, cooling mode approx. 14 kW)
Connections
To mould 1 1/4″ BSP female thread
From mould 1 1/2 ” BSP female thread
Automatic water refill 3/8 ” BSP female thread
Drain 1 ” BSP female thread
Cooling water in/out 1 ” BSP female thread (only at WK)
Dimensions (L×W×H) 1’350 × 1’050 × 1’950 mm, incl. feets
Noise Level(in 3 m distance) 65 dBA
Weight 585 kg empty
Color silvergrey RAL 7001

Also Available: